Battery Storage Failures Plunge 98% in Seven Years: Why Older Sites Still Pose Heavy Financial and Safety Risks

A comprehensive EPRI study reveals battery storage failure rates dropped 98% from 2018 to 2025, but pre-2021 installations face urgent retrofit dilemmas and warranty traps.

Published: 2026.10.14

The 98% Safety Turnaround: How Battery Storage Solved Its Early Fire Crisis While Inheriting a 3% Legacy Problem

Utility-scale batteries have spent the last seven years rewriting their reputation with fire marshals, insurance underwriters, and grid operators. Between 2018 and 2025, global failure rates across battery energy storage systems (BESS) plummeted by 98%, according to comprehensive research published by the Electric Power Research Institute (EPRI). What was once treated as an unpredictable operational hazard has settled into a mature, heavily engineered asset class. Over 93% of all recorded battery incidents worldwide caused zero injuries and zero fatalities, and the United States has not recorded a single death or injury from a battery failure since the spring of 2019.

The turning point traces back directly to April 2019, when a battery rack experienced thermal runaway at an Arizona Public Service (APS) facility in Surprise, Arizona. When first responders opened the door of the containerized building, built-up flammable gases met fresh air and triggered a catastrophic explosion that severely injured four firefighters. That single disaster forced the energy storage sector to confront an uncomfortable fact: early battery plants were designed around simple fire suppression—like dousing flames with water—rather than managing the build-up of explosive gas clouds inside tight boxes.

The industry responded by rewriting the rulebook. Safety engineers created NFPA 855, the definitive national standard for installing stationary energy storage systems. NFPA 855 mandated cell-level thermal barriers, active gas venting, explosion relief panels, and generous spacing between individual enclosures. Batteries installed over the past five years reflect these hard lessons. They catch cell defects early, isolate hot cells before heat hops to neighboring modules, and vent volatile gases out the roof long before pressures can rupture steel walls.

Yet this dramatic safety leap leaves a stubborn blind spot. Roughly 3% of all global battery capacity currently in service came online before 2021. While 3% sounds like a negligible rounding error on a global balance sheet, these aging installations represent thousands of megawatt-hours of operating assets. Most of them were built before modern standards took effect. They sit near suburban substations, inside retired fossil fuel plant turbine halls, and on commercial campuses. For the asset managers running these older sites, good news for the broader industry does not solve their everyday reality. They face steep insurance renewal hikes, stricter municipal fire audits, and difficult technical choices on whether to spend millions on retrofits or bulldoze the facility early.

Global Battery Energy Storage Safety Benchmarks (2018-2025)

Key takeaways from the Electric Power Research Institute (EPRI) safety review

-98%

Failure Rate Drop

Decline in system-level failures per gigawatt-hour installed between 2018 and 2025

93%

Zero-Casualty Rate

Proportion of global BESS safety incidents that resulted in no injuries or fatalities

3%

Legacy Capacity Share

Global operating capacity built before 2021 that operates under outdated design baselines

The scale of legacy exposure became painfully clear in January 2025 at the Moss Landing energy facility in California. Operators had installed a massive 300-megawatt battery array inside a decommissioned 1950s power plant turbine hall in 2020. When an internal cell fault triggered thermal runaway inside one of the indoor racks, heat and toxic smoke spread across the indoor hall. The resulting fire gutted most of the facility and billowed thick smoke across Monterey County for days.

While environmental testing confirmed no long-term toxic contamination in local soil or drinking water, and no personnel suffered physical injuries, the financial loss was staggering. It destroyed hundreds of millions of dollars in equipment, shut down vital grid-balancing capacity, and proved once again that indoor, warehouse-style battery banks carry far more operational risk than modern outdoor modular cabinets. The incident demonstrated that the gap between pre-2021 installations and modern systems is not cosmetic; it is an architectural chasm.


Pre-2021 Vintages vs Modern Modular Arrays: A Side-by-Side Breakdown of Failure Rates and Capital Risks

To understand why failure numbers collapsed so quickly, facility operators must compare the fundamental differences in how systems were built before 2021 versus how they are engineered today. Early battery developers treated batteries like server racks: they packed as many lithium-ion cells as possible into single, enclosed rooms or retrofitted shipping containers to minimize installation costs. Modern projects treat every cluster of cells as an independent, outdoor chemical reactor designed to fail safely without touching its neighbors.

The operational differences show up across containment architecture, gas management, permitting lead times, and operating expenses.

Operational MetricPre-2021 Legacy InstallationsPost-2021 Modern InstallationsPractical Impact on Plant Operators
Typical Housing ArchitectureCentralized indoor halls or tightly packed walk-in shipping containersDecentralized, outdoor modular enclosures (pad-mounted cubes)Indoor setups face up to 4x higher property loss during an incident due to heat trapping
Cell Propagation ControlBasic module separation; heat easily jumps between adjacent cellsTested UL 9540A barriers; non-propagating ceramic and aerogel shieldingThermal runaway remains confined to a single 50-kWh string instead of burning the whole array
Gas Detection & ExhaustLate-stage smoke detectors and basic ceiling HVAC louversEarly off-gas detection (VOC/hydrogen sensors) with active mechanical exhaustEliminates the build-up of explosive gas pockets before personnel open access doors
Deflagration VentingSide-facing burst panels or unreinforced steel doorsUpward-directed blast roofs and roof-mounted pop-off panelsDeflects overpressure waves into empty sky, protecting first responders and transformers
Average Permitting Cycle3–6 months (grandfathered under basic electrical codes)9–18 months (subject to strict NFPA 855 audits and third-party safety reviews)Modern safety compliance takes longer upfront but prevents costly stop-work orders later
Annual Insurance Premium$28,000–$45,000 per MW installed (with high deductibles and exclusions)$12,000–$18,000 per MW installed (under standard commercial casualty policies)Older facilities pay nearly double in risk premiums to offset total-loss exposure
Simulated Retrofit Cost$65,000–$140,000 per MW to add sensors, exhaust, and blast redirectionBuilt into base capital expenditure ($0 field modification penalty)Retrofitting older sites can quickly erode three to five years of operational earnings

Note: Figures above reflect industry averages, modeled operational estimates, and EPRI research benchmarks across commercial utility-scale lithium-iron-phosphate (LFP) and nickel-manganese-cobalt (NMC) facilities.

Modern systems achieve low failure rates primarily through early detection. When a lithium-ion cell begins to fail internally, it releases distinct volatile organic gases and trace hydrogen minutes before its internal temperature spikes. Pre-2021 systems relied on standard optical smoke alarms or heat cables. By the time a traditional smoke detector sounded the alarm, the cell was already well past its boiling point, releasing thick flammable vapor and igniting neighboring cells like dominos.

Contemporary installations monitor off-gas signatures down to parts-per-million concentrations. If an anomalous gas signature appears, the automated safety system immediately disconnects the electrical contactors for that specific rack, trips the localized cooling circuit, and activates high-speed exhaust fans to sweep volatile vapors outdoors. The problem is isolated at the component level before open flames can ever appear.


What Legacy Assets Cost Plant Operators: Operational Hazards, Warranty Cliffs, and Structural Enclosure Traps

The sharp decline in top-line industry failure rates masks serious operational headaches for asset owners managing older systems. These facilities continue to age in an environment where regulators, insurers, and municipal fire chiefs hold them to modern performance expectations. Operators managing early-generation sites run into three persistent roadblocks.

Escalating Insurance Premiums and Uninsurable Indoor Footprints

The Moss Landing incident made commercial property underwriters extraordinarily cautious about indoor battery projects. When batteries burn inside an enclosed turbine hall or warehouse, temperatures can exceed 1,000 degrees Celsius within minutes. Steel roof trusses warp, concrete walls crack, and toxic fumes linger for days, preventing cleanup crews from safely entering the site. For an insurance carrier, an indoor fire almost always represents a 100% total loss of both the building and the electrical equipment inside.

As a result, insurance underwriting for pre-2021 indoor assets has hardened significantly. Operators report that deductibles for thermal runaway claims have doubled or tripled, while annual premiums consume an increasingly large share of total operational earnings. In some jurisdictions, carriers refuse to underwrite legacy indoor systems unless the plant owner installs extensive sub-division walls, blast partitions, and automated deluge systems. In competitive power markets where batteries earn money on narrow arbitrage spreads and ancillary service contracts, these insurance surcharges wipe out thin operating margins.

The Flammable Gas Dilemma: Why Explosion Mechanics Eclipse Fire Risks

Fire is dangerous, but fire alone rarely kills first responders who keep a safe perimeter. Explosion, on the other hand, is an existential hazard. When battery cells break down, they release a fuel-rich cocktail of hydrogen, carbon monoxide, methane, and vaporized organic solvents. If this mixture stays inside a sealed enclosure without burning immediately, it only needs a tiny electrical arc or static spark to detonate.

The resulting pressure wave can blow heavy steel doors off their hinges, turn sheet metal into shrapnel, and collapse nearby control rooms. EPRI’s findings highlight that addressing this deflagration risk requires far more than sticking a fire extinguisher on the wall. Plant operators must keep combustible gas concentrations well below 25% of their lower flammability limit (LFL).

Installing gas detection is relatively straightforward and affordable. However, moving massive volumes of air through a tightly packed battery shipping container during a crisis requires heavy-duty ductwork, spark-proof exhaust fans, and engineered air intake paths. If an enclosure lacks these airflow paths from day one, adding them later means cutting through weather seals, thermal insulation, and fire-rated walls.

The Warranty Trap: How Modifying Enclosures Voids OEM Guarantees

When an asset manager decides to fix an older battery bank by adding modern safety hardware, they walk straight into a legal trap. Most utility-scale battery systems come with 10-year to 15-year performance warranties and capacity maintenance agreements from original equipment manufacturers (OEMs). These long-term agreements guarantee that the cells will hit specific round-trip efficiency marks and capacity retention targets over thousands of charge-discharge cycles.

Making major field modifications—such as cutting new vents into the enclosure walls, replacing structural roof latches with upward-opening blast panels, or tapping into the original battery management system (BMS) wiring to trigger third-party fans—often breaches the manufacturer’s strict operating terms.

Once an operator cuts into an enclosure envelope, the manufacturer can void the capacity warranty, walk away from degradation guarantees, and refuse to provide replacement modules. Operators find themselves caught between two unacceptable choices: leave an older system in place with high explosion risks, or upgrade the safety hardware and shoulder all future battery degradation risks without manufacturer backing.

The Legacy BESS Retrofit Dilemma

Balancing safety improvements against contractual and balance-sheet liabilities

Benefits of Safety Retrofits

  • ✓ Dramatically cuts deflagration and explosive overpressure risks
  • ✓ Lowers property casualty insurance premiums by 20% to 35%
  • ✓ Reduces the likelihood of catastrophic shutdown orders from local fire marshals

Liabilities and Capital Costs

  • • Field cuts and wiring modifications can void OEM capacity warranties
  • • High engineering expenses ($65,000–$140,000 per MW installed)
  • • Requires prolonged operational downtime during system recertification

Outdoor Modular Packaging and Blast Deflection: How Modern Architectures Prevent Thermal Runaway Cascades

The 98% plunge in battery failures did not happen by accident. It is the direct result of a wholesale shift in how energy storage hardware is packaged and deployed. The industry has largely abandoned the concept of walking inside battery rooms. Instead, modern installations use sealed, modular outdoor cabinets that function like secure shipping safes lined up on concrete pads.

Pre-2021 Warehouse Arrays vs Modern Modular Outdoor Arrays

How physical architecture changed the game for battery risk management

Legacy Indoor Warehouse Array

High Cascade Risk
  • • Batteries share common indoor air space across hundreds of megawatt-hours
  • • Heat and smoke accumulate inside the building, feeding secondary fires
  • • First responders must enter toxic, potentially explosive confined spaces
  • • A single unit failure can lead to total asset destruction

Modern Outdoor Modular Pod

Engineered Isolation
  • • Small, self-contained steel cubes (typically 2 to 4 MWh per unit)
  • • UL 9540A-tested non-propagating walls between neighboring pods
  • • Roof-mounted deflagration panels direct blast forces straight up
  • • Emergency crews fight fires from a safe distance without entering enclosures
Editorial Verdict: Decentralized outdoor pods limit catastrophic losses to a single isolated container while keeping maintenance and emergency personnel completely out of harm's way.

In a contemporary outdoor pod installation, cells are arranged in narrow, thermally isolated columns. Ceramic blankets and aerogel barriers sit between each module. If cell manufacturing defects or electrical short circuits cause an individual pouch or prismatic can to overheat, the thermal energy is swallowed by the protective barrier. The adjacent cell stays cool enough to avoid crossing its thermal runaway threshold.

Equally important is how modern enclosures handle mechanical overpressure. Instead of building rigid, airtight containers that act like pressure cookers when gases ignite, engineers design roofs with calculated weak points. If flammable gases ignite inside a cabinet, calibrated roof latches pop open within milliseconds.

The entire explosive force vents vertically into the open sky, away from nearby battery pods, transformers, control trailers, and emergency workers standing on the ground. The fire burns itself out inside its dedicated metal shell, sparing the rest of the 500-megawatt-hour facility from secondary damage.

This modern safety architecture also changes how regional authorities grant project approvals. While early projects were pushed through under broad commercial building rules, permitting has become much more thorough. Because the national NFPA 855 standard sets strict baseline caps on unit size and spacing, developers regularly file for technical exemptions to build higher-density, more cost-effective installations.

To help volunteer fire departments and small town zoning boards evaluate these complex technical filings, states are changing their legal frameworks. In New York, an updated state fire code requires energy storage developers to pay for independent, third-party engineering reviews of their exemption filings. This ensures that every high-density project receives thorough scrutiny from certified safety scientists before a single concrete pad is poured.


The Operator Defense Framework: Three Guardrails for Auditing and Retiring High-Risk Energy Storage Assets

Because older batteries cannot be magically turned into 2026-vintage hardware, plant owners need a clear, disciplined approach to manage their risk. Pretending that early-generation systems carry the same safety profile as modern modular cabinets is a recipe for operational disaster. Operators managing pre-2021 energy storage assets should implement a structured, three-tier defense framework to protect their capital and personnel.

First Line of Defense: Immediate Gas Detection and Thermal Imaging Audits

The fastest, most cost-effective safeguard for an aging facility is closing the gap between when a cell begins to fail and when operators find out about it. Facility teams must review every legacy enclosure to ensure off-gas detection operates independently of general fire alarms.

  • Deploy Multi-Gas Sensor Arrays: Install standalone volatile organic compound (VOC) and hydrogen detectors directly above battery racks. These sensors detect early electrolyte breakdown minutes before temperature sensors register heat increases.
  • Run Automated Infrared Scans: Mount fixed radiometric thermal cameras or run bi-weekly drone thermal sweeps over older outdoor containers. Catching localized cell hot spots or loose busbar connections during routine high-rate cycling prevents gradual thermal degradation from becoming an emergency.
  • Isolate HVAC Recirculation Loops: For older walk-in enclosures, ensure HVAC systems do not pull air from one battery bank and blow it across adjacent racks. Closed recirculation loops turn localized off-gassing into building-wide explosive mixtures within minutes.

Second Line of Defense: Passive Blast Deflection and Enclosure Boundary Retrofits

If an older installation houses batteries in walk-in containers or repurposed buildings, owners must reassess how the facility manages mechanical overpressure. Relying on side-swinging escape doors to relieve explosion pressure endangers anyone standing nearby.

  • Install Roof-Venting Relief Hatches: Where structural framing permits, replace rigid roof sections with engineered blast panels. These panels must release at pressures far lower than the wall structural integrity limits, ensuring explosive energy goes upward rather than outward.
  • Erect Physical Fire Barriers Between Blocks: If older units are spaced less than ten feet apart without certified non-propagation barriers, install exterior thermal blast walls (such as reinforced masonry or heavy-gauge steel-faced fire barriers). This stops a fire in one container from scorching the adjacent unit’s exterior shell.
  • Clear First-Responder Safety Corridors: Update standard operating procedures with local fire districts. First responders must never open the doors of an active legacy enclosure experiencing off-gassing. Install external emergency purge switches and water hookups so firefighters can flush enclosures with inert gas or soak them with high-volume water from outside the blast zone.

Third Line of Defense: The Decommissioning Calculus Over Voided Warranties

Retrofitting an aging battery is not always smart business. Facility owners must run the financial numbers with brutal honesty. If bringing an early-vintage asset up to an acceptable safety baseline requires structural modifications that void the OEM’s capacity warranty and cost upwards of $100,000 per megawatt, continuing to operate the system is often an irresponsible gamble.

The Legacy BESS Decommissioning Decision Flow

Determining whether to retrofit, restrict, or retire aging energy storage assets

1

1. Asset Baseline Audit

Inspect enclosure venting, off-gas sensors, and proximity to occupied buildings

2

2. Contract & Warranty Check

Review whether needed enclosure cuts will void manufacturer capacity guarantees

3

3. Insurance & Capex Balance

Compare retrofit expense against rising annual insurance premiums and loss reserves

4

4. Final Strategic Determination

Choose between full retrofit, derating operational cycles, or early repowering

When evaluating systems commissioned prior to 2021, asset managers should apply three decisive retirement rules:

  • The Space Containment Threshold: If the installation sits indoors within a shared structure—such as an active warehouse, occupied commercial building, or legacy turbine hall—and cannot be compartmentalized into small, fire-rated rooms, plan for orderly early decommissioning. The risk of total structural loss and lingering liability outweighs ongoing power market revenues.
  • The Capital Parity Test: Compare the all-in cost of structural retrofits, new gas exhaust systems, recertification fees, and higher insurance premiums against the declining capital cost of modern outdoor modular hardware. If retrofits cost more than 40% of what it would take to repower the pad with brand-new, warranty-backed modular units, decommission the legacy hardware and repower the site.
  • The Cycle Restriction Compromise: If an asset is financially viable but cannot receive structural retrofits due to warranty limits, immediately derate its operating profile. Restricting the battery’s state of charge (SoC) operating window from 0–100% down to 10–85%, while capping charge and discharge C-rates, significantly reduces the physical stress on aging lithium-ion cells. This limits thermal runaway triggers until the plant reaches the end of its contractual power purchase agreement.

The battery storage sector has proven it can engineer its way out of early safety pitfalls. A 98% reduction in catastrophic failures shows what happens when rigorous manufacturing, intelligent sensing, and tough installation codes work together. But as thousands of gigawatt-hours of modern equipment roll onto the grid every month, asset managers cannot afford to ignore the early pioneers of the storage revolution. Giving legacy facilities the specialized audits, retrofits, or retirement plans they require is the only way to ensure the industry’s hard-won safety reputation stays intact.